Description
8808 Technical Data Sheet – Belden Global Catalog
Product Description
8 AWG (19×21) bare copper conductors, PVC/nylon insulated, twisted pair, unshielded, PVC jacket, rip cord
Technical Specifications
Product Overview
Environmental Space: Indoor/Outdoor
Suitable Applications: Auditorium, Stadium, Race Track, Church, Temple, Synagogue, Place Of Assembly, Casino, Sound
Physical Characteristics (Overall)
Conductor
AWG Stranding Material No. of Conductors
8 19x21H BC – Bare Copper 2
Conductor Count: 2
Insulation
Layer Material
1 PVC – Polyvinyl Chloride
2 Nylon
Outer Shield Material
Material
Unshielded
Outer Jacket Material
Material Nominal Diameter
PVC – Polyvinyl Chloride 0.57 in
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR
0.66 Ohm/1000ft
Voltage
UL Voltage Rating
600 V
Temperature Range
Operating Temp Range: -30°C To +90°C Dry; -30°C To +75°C Wet
Wet Temp Range: -30°C To +75 °C
Dry Temp Range: -30°C To +90°C Dry
Mechanical Characteristics
Bulk Cable Weight: 180 lbs/1000ft
Max Recommended Pulling Tension: 352 lbs
Min Bend Radius/Minor Axis: 5.75 in
Standards
NEC/(UL) Specification: NPLF, TC, THHN/THWN Singles
CPR Euroclass: Eca
Applicable Environmental and Other Programs
EU Directive 2011/65/EU (ROHS II): Yes
EU Directive 2012/19/EU (WEEE): Yes
EU Directive Compliance: EU Directive 2002/96/EC (WEEE)
EU RoHS Compliance Date (yyyy-mm-dd): 2012-03-15
CA Prop 65 (CJ for Wire & Cable): Yes
Suitability
Suitability – Burial: Yes
Suitability – Indoor: Yes
Suitability – Outdoor: Yes
Suitability – Sunlight Resistance: Yes
Flammability, LS0H, Toxicity Testing
UL Flammability: UL1581 Vertical Tray
CSA Flammability: FT4
ISO/IEC Flammability: IEC 60332-1-2
IEEE Flammability: 1202
UL voltage rating: 600 V RMS
Plenum/Non-Plenum
Plenum (Y/N): No
Part Number
Variants
Item # Color UPC Length
8808 0101000 Black 612825408895 1,000 ft
8808 0105000 Black 612825216582 5,000 ft
History
Update and Revision: Revision Number: 0.255 Revision Date: 01-31-2020






Reviews